Type 300 M Electronic Unit Specification

 

   
logo 1 or 2 Point Steam / Water Level Detection 300M
logo Process Fault Indication
logo Probe Fault Indication
logo 3 Relay output
logo Single Power Supply
logo Loss of Hydrogen Coolant etc.
 
 
 

 

The principle of resistance probe discrimination between water and steam is well established and accepted by the Power Plant industry as the most reliable, convenient and maintenance free method of detecting alarm levels and initiating protective actions. 2 independent probe channels in one electronic enclosure means the installed cost per detection point can be appreciably lower than traditional float level switches.

The system incorporates a probe fault circuit that can distinguish whether probes are in a healthy state. The process fault circuit indicates a change in the normal operating state of each probe (e.g. from steam to water) The Probe Insert Assembly is welded into pipework or vessels at the selected detection points. This provides internal shrouding of the probe for defined water conductivities and a robust housing for external protection of the probe.

Multiple Probe Pipework Assemblies can be supplied to suitparticular applications. Advice always available and special applications considered.

Pressure Parts
Type 801 Probe, rating 150 bar @ 340°C, requires Insert Assembly Type 701.
Type 802 Probe, rating 207 bar @ 370°C, requires Insert Assembly Type 702.
Versions of the above Probes with non-wetting PTFE insulators are available for low and high water conductivity. Rating 50 bar @ 220 °C.


Electronic Unit Specification:
Enclosure: Wall mounted glass-fibre reinforced polyester. Protection IP65/NEMA 4X.
Dims: 200H x 120W x 100D.


Inputs:
Discrimination between water and steam for 2 independent isolated channels. Switching threshold selected for water conductivities of 0.5, 1 or 2mS/cm.
Probe cable monitoring to suit water or steam normal condition for each channel.


Outputs:
Selection for Relays energised in the Safe plant condition. Two pole changeover contacts per channel. Single pole Changeover contact for System Fault.
Contact Rating: Max Voltage - 250Vac, 220Vdc
Max Current - 8Amps
Load Switching - 240W / 2000 VA.
Display: LED indication on each channel, illuminated Red for abnormal (alarm) state. Yellow LED indication for Process Fault and 1 for Probe Fault. The selection of horizontal, vertical or combination configurations of probe channel validations, or Mains Supply failure initiates the System Fault indication. Green LED illuminated when both Mains Supplies are healthy.

Supply Requirements:
Single AC Power Supply
92 - 127V @ 15VA, 48 - 63Hz
184 - 254V @ 15VA, 48 - 63Hz
Temperature Rating: -10 to 65 °C Amb.
-50 to 100 °C Storage.